IPI, IC695PBM300 - PROFIBUS Master Module ka31A000000HAkeQAG | GE Customer Center

IPI, IC695PBM300 - PROFIBUS Master Module

Rel.Ver.DateIPIUpgrade KitNew FeaturesProblems Resolved
CC1.04Jun-2010GFK-2359D44A753033-G01N/AN/A - Label change only. No change in functionality, performance or compatibility.
BC1.04May-2006GFK-2359C44A753033-G01N/A

When multiple Lumberg devices (8in4out) are connected to the bus and power is removed from these devices, but the PBM300 remains powered, the inputs assigned to the Lumberg devices will toggle between 1 and 0.

Configuring slaves with a large amount of parameter data returns the correct error code when parameter data exceeds the available memory space.

BB1.02Apr-2005GFK-2359B44A753033-G01The number of Message Segments used to hold mail messages has been doubled from 32 to 64.When a Get Master Status CommReq is called on the first PLC scan, the CommReq no longer falsely returns a positive indication that the Profibus network has ý1 or More Slaves Not in IO Exchange Mode.ý
BA1.00Feb-2005GFK-2359ANAUL Class I, Groups A, B, C & D, Div 2 Hazardous LocationsNA
AA1.00Dec-2004GFK-2359N/AInitial Release of ProductInitial Release of Product